XHHW / XHHW-2 / XHH / SIS (with UL Style)

 

Construction

  • Conductor:                  bare or tinned copper, bunch stranded
  • Core insulation:            flame retardant cross-linked halogen free compound
                                according to table 11 UL 44 (type XL)
  • Core identification:        different colours
  • Single core assembly for
    "Submersible Pump Cable”:   from two up to six wires cabled of type XHH
                                or XHHW or XHHW-2 together without overall jacket
  • Marking:                    printing according to UL and manufacturer specifications,
                                production date and traceability code
  • Range of approval:          from AWG14 up to kcmil 2000, in any colour (type SIS up
                                to AWG 4/0); intermediate cross-section, such as AWG13,
                                AWG11…, are available

 

Properties

  • Fire behaviour:             horizontal flame test
  • halogen free

 

Technical Data

  • Thermoset insulated wire rated 600V to feed submersible pumps
  • Minimum installation
    temperature:                - 25°C
  • Minimum operating
    temperature:                - 40°C

                     
                      operating                operating
       type            voltage                temperature
    -----------------------------------------------------------

       XHHW-2            600V               90°C wet or dry
       XHHW              600V            75°C wet and 90°C dry
       XHH               600V                  90° dry 
       SIS               600V                  90° drY

       
        Tolerance on           Outer diameter
       outer diameter               [mm] 
    -------------------------------------------------
         +/- 0,20                   ≤ 5
         +/- 0,25             from 5,1 up to 10
         +/- 0,30             from 10,1 up to 15
         +/- 0,35             from 15,1 up to 25

 


Cross-section [AWG] Nominal outer diameter [mm] Cu-Weight kg/km min. insulation res. Ω//km Electrical res. (Ω//km) at 20°C (untinned) Electrical res. (Ω//km) at 20°C (tinned) Inductance [mH/km] Ampacity at air temperature 30° based on NEC [A] Article Number
14 3,5 21 810 8,70 9,24 0,086 25 22044014
12 4,0 33 680 5,48 5,81 0,076 30 22044012
11 4,3 45 560 4,35 4,61 0,071 35 22044011
10 4,6 52 560 3,45 3,66 0,067 40 22044010
9 5,7 70 650 2,73 2,90 0,076 45 22044009
8 6,1 81 650 2,16 2,30 0,072 55 22044008
7 6,7 110 540 1,71 1,79 0,067 60 22044007
6 7,1 125 540 1,37 1,42 0,064 75 22044006
5 8,0 170 450 1,08 1,12 0,061 80 22044005
4 8,7 201 450 0,857 0,890 0,056 95 22044004
3 9,5 281 400 0,679 0,707 0,053 110 22044003
2 10,3 317 370 0,539 0,560 0,054 130 22044002
1 12,0 400 390 0,431 0,449 0,051 150 22044001
1/0 13,0 500 350 0,342 0,355 0,050 170 22044100
2/0 14,3 631 320 0,271 0,282 0,047 195 22044200
3/0 15,9 792 290 0,215 0,223 0,044 225 22044300
4/0 17,7 996 260 0,170 0,177 0,042 260 22044400