Aquamate - round cables for waste water immersion
Construction
- Conductor: Bare cooper complying with CEI EN 60228
Class 5 - Core insulation and
identification: XLPE
Up to 5 cores according to HD 308 S2
From 6 cores black numbered with green/yellow
(VDE 0293-JZ) - Jacket: CPE elastomer
Colour black RAL 9005
Technical Data
- Operating voltage: 0,6/1kV
- Insulation resistance: > 200 MΩ.Km
- Operating temperature:
- Fixed application: - 40°C to 85°C
- Min. Installation
temperature: - 25°C
- Max. temperature
in water: + 40°C
- Max. temperature
on conductor: + 90°C - Maximum tensile force:
- Fixed application: 4 x outer diameter
- Flex. application: 6 x outer diameter - Min. bending radius:
- Fixed application: 5 x outer diameter
- Flex. application: 6 x outer diameter
Properties
- Resistance to mineral oils: According to EN 50363-2-2
- Resistance to water: According to AD8
- Constructions standards: EN 50525-2-21,
IEC 60502-1, EN 50363 - UV resistant
cores x cross-section [mm] | nominal diameter [mm +/- 5%] | Cu-Weight [Kg/km] | cable mass [Kg/km] | Article Number |
---|---|---|---|---|
1x1,5 | 5,8 | 15 | 43 | 6505011510 |
2x1,5 | 9,2 | 28,8 | 114 | 6505021510 |
3G1,5 | 9,7 | 43,2 | 111,5 | 6505031510 |
4G1,5 | 10,6 | 57,6 | 136,5 | 6505041510 |
7G1,5 | 15,1 | 101 | 280 | 6505071510 |
12G1,5 | 18,3 | 173 | 420 | 6505121510 |
18G1,5 | 21,4 | 260 | 593 | 6505181510 |
24G1,5 | 25 | 346 | 785 | 6505241510 |
- Weitere Anfertigungen auf Anfrage
- Alle Angaben ohne Gewähr
- Sollten Sie Fragen zu diesem Produkt haben, können Sie uns gerne telefonisch oder über unser Kontaktformular erreichen.
Datenblatt herunterladen