Combi CanBus 1x2x0,64+4x1,5 (L) 2YS2Y sw/9005

                                    

Construction 1x2x0,64 

 

  • Conductor:                         Bare solid copper wire
                                       diameter around 0.64 mm; Cross-section around 0.32 qmm
  • Insulation:                        Polyethylene foam skin according to DIN EN 50290-2-23
  • Core colours:                      green-red
  • Stranding:                         2x core and 2x filler/filler for VVB
  • Wrapping:                          1 layer of plastic film, overlapped, running lengthwise
  • Shield:                            One layer of aluminum composite foil, overlapped, running lengthwise
                                       Aluminum sides on the outside, braiding of tinned copper wires
                                       single wire diameter 0.1 mm; optical coverage > 60%
  • Sheath:                            PVC mixture according to DIN EN 50290-2-22
                                       Colour: violet - RAL 4001

 

Construction 4x core 1,5 qmm

 

  • Conductor:                         bare copper wires; Wire 30x0.25mm
                                       diameter around 1.6 mm; Cross-section around 1.5 qmm
  • Insulation:                        PVC mixture according to DIN EN 50290-2-21
  • Core colour:                       3 x black + number printing white; 1x green-yellow

 

Construction VVB + (L)2YB2Y

 

  • Stranding:                         Profibus 1x2x0.64 + 4x core 1.5 mm² + 9x filler/filler
                                       to the stranding association (VVB); Arrangement variable0
  • Wrapping:                          At least one layer of plastic film, overlapped
                                       (longitudinal or braided)
  • Layered jacket:                    Polyethylene-coated, longitudinally running aluminum tape and
                                       Sheath: Polyethylene L/MD according to DIN EN 50290-2-24
                                       wall thickness: 1.2 ± 0.2mm; Colour: black - RAL 9005
  • Reinforcement:                     one layer of galvanized steel strip; Thickness: 0.2mm; Space about 2 mm
  • Protective cover:                  Polyethylene L/MD according to DIN EN 50290-2-24
                                       wall thickness: 1.4 ± 0.2mm; Colour: black - RAL 9005
  • Dimensions:                        Outer diameter: approx. 19.4 ± 0.8 mm (RW)
                                       Weight: around 375 kg/km (RW)

 

Properties / operating conditions 1x2x0.64:

 

  • Loop conductor resistance:          115 Ω/km max
  • Insulation resistance:              5 GΩxkm min
  • Operating capacitance:              30nF/km max
  • Characteristic impedance:           150 ± 15Ω
  • Coupling loss:                      > 80dB
  • Coupling resistance at 10MHz:       < 20mΩ/m
  • Test voltage:                       1500 V - 50 Hz - 1 min
  • Peak Operating Voltage:             250V

 

Properties / conditions of use core 1.5 qmm:

 

  • Conductor resistance:              13.3 Ω/km max
  • Insulation resistance:             20 MΩxkm min
  • Test voltage:                      3000 V - 50 Hz - 1 min
  • Rated voltage U0/U:                300 / 500 V

 

Properties / conditions of use

 

  • Temperature range:                 flexible -20 °C to +50 °C
                                       permanently installed max. +70 °C
  • Bending radius:                    15x cable diameter

 

Special cable with rodent protection and protective cover
Laying in cable ducts and ducts as well as outdoors and in the ground; Cross-waterproof cable core

 

Article number: 44302S6410


  • Weitere Anfertigungen auf Anfrage
  • Alle Angaben ohne Gewähr
  • Sollten Sie Fragen zu diesem Produkt haben, können Sie uns gerne telefonisch oder über unser Kontaktformular erreichen.

Datenblatt herunterladen