YCY-JZ (OZ) 0,6/1, black 0,50 - 0,75 mm²

                                   Flexible, UV-resistant control cable with overalll copper
                                     braided screening; preferred EMC compatible cable type

 

Construction

 

  • Conductor:                 stranded bare Cu conductor, fine wire
  • Construction:              strand structure to VDE 0295, class 5 / IEC 60228 class 5
  • Core insulation:           special PVC
  • Black cores with printed consecutive white number coding
  • Protective conductor:
    JZ = green-yellow protective conductor in the outer layer (3 cores and over)
    OZ = without protective conductor
  • Cores twisted in layers, with optimal lay lengths
  • Special PVC inner jacket, black
  • Braided Screening made of tinned copper wires
  • Outer sheath:              special PVC, flame retardant and UV-resistant
  • Sheath color:              black, RAL 9005

 

Technical Data

 

  • Rated voltage:             Uo/U        600/1000 V
  • Test voltage:              4000 V
  • Insulation resistance:     ≥ 20 MOhm x km
  • Bending radius:            20 x cable diameter
  • Temperature range:
                               flexible     -5°C to +70°C
                               stationary  -30°C to +70°C

 

Properties

 

  • Flame retardant acc. to IEC 60332-1

Ø mm² Cu-Weight kg/km Outer diameter mm Total-Weight kg/km Article number
5 x 0,5 62,0 11,6 239,0 472 + no. of cores + diameter
2 x 0,75 OZ 46,0 10,5 183,0 472 + no. of cores + diameter
3 x 0,75 56,0 10,9 210,0 472 + no. of cores + diameter
4 x 0,75 67,0 11,4 238,0 472 + no. of cores + diameter
5 x 0,75 78,0 12,1 272,0 472 + no. of cores + diameter
7 x 0,75 97,0 12,9 315,0 472 + no. of cores + diameter
12 x 0,75 168,0 15,8 464,0 472 + no. of cores + diameter
18 x 0,75 229,0 18,0 616,0 472 + no. of cores + diameter
25 x 0,75 296,0 20,7 762,0 472 + no. of cores + diameter