PROFIBUS for underground installation
UV-resistant cable for Sinec-L2-DP and FIP (Factory Instrumentation Protocol)
Construction
- Conductor: bare Cu wire
- Core insulation: expanded PE
- Core colours: red and green
- Cores twisted in layers, with optimal lay lengths
- Overall screening with composite aluminium foil, metal layer on the outside,
and tinned copper braided Screening - Inner jacket: special PVC, flame retardant
- Outer sheath: PE, UV-resistant
- Sheath colour: black
Technical Datas
- Peak operating voltage: max. 100 V
- Test voltage: 3600 V/3 sec.
- Conductor loop resistance: max. 110 V Ohm/km
- Insulation resistance: ≥ 16000 MOhm x km
- Mutual capacitance at 1 kHz: approx. 28.5 nF/km
- Bending radius: single bending min. 150 mm
repeated bending min. 300 mm - Temperature range: -40°C to +60°C
- Wave impedance: nominal value 150 Ohm
3 to 20 MHz 150 ± 15 Ohm
38.4 kHz 185 ± 18.5 Ohm
9.6 kHz 270 ± 27 Ohm - Attenuation: at 16 MHz < 45 dB/km
at 4 MHz < 22 dB/km
at 38.4 kHz < 5.0 dB/km
at 9.6 kHz < 3.0 dB/km
Available special types
- with tinned Cu wire
- with steel tape armouring, type 02Y(St)CY(B)2Y, outer diameter approx. 10.8 mm
Ø mm² | Cu-Weight kg/km | Outer-Ø mm | Total-Weight kg/km | Article number |
---|---|---|---|---|
1 x 2 x 0.64 | 26.3 | 10.2 | 85.0 | 4431206401 |
- Weitere Anfertigungen auf Anfrage
- Alle Angaben ohne Gewähr
- Sollten Sie Fragen zu diesem Produkt haben, können Sie uns gerne telefonisch oder über unser Kontaktformular erreichen.